Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/21/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL SUBJECT TO OTHER INSPECTION. |
| 07/11/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) #8 ROMEX CABLE HAS AN ALLOWABLE AMPACITY OF 40 AMPS PER CODE 336-26,310-15. 2.) MAINTAIN WORKING AREAS AT A/C DISCONNECTS 110-26. |
| 07/09/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1.) A BOX IS NEEDED AT BATH FIXTURES AND GROUND FIXTURES 2.)METAL EXTENDER RINGS ARE NOT LISTED PLEASE USE AN APPROVED RING 3.) WE HAVE A WORKING CLEARENCE AND DEDICATED SPACE VIOLATION AT A/C DISCONNECT. 4.) FINISH WALK WAY LIGHTING. |
| 07/03/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |