Permit: T01CM04393

Parcel: 105131200

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/21/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL SUBJECT TO OTHER INSPECTORS.
07/17/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*HEAT STRIPS TO BE REMOVED ROOF OK FOR CLEARENCE.
07/11/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) #8 ROMEX CABLE ALLOWED AMPACITY IS 40 AMPS PER CODE 336-26, 310-5 2.) WE HAVE WORKING CLEARENCE VIOLATIONS AT A/C DISCONNECT.
07/10/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1.) PLEASE USE AN APPROVED EXTENDER RING. 2.) WE HAVE A DEDICATED SPACE VIOLATION AT A/C DISCONNECT OK TEMP POWER FOR TEST SUBJECT TO LAST INSPECTOR.
07/03/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.)INSTALL HOODS 2.) FINISH CUTTING OUT AROUND RECEPTACLE AND PROVIDE AN APPROVED EXTENDER RING AT GARBAGE DISPOSAL. 3.) SUPPORT FLEX AND TIGHTEN FITTINGS AT WATER HEATER. 4.) GROUND BATH FIXTURE 5.) LABEL PANEL 6.) FINISH INSTALLATION OF PLATES. 7.) INSTALL GROUNDS AT GROUND BAR AS PER MANFACTURES INSTRUCTIONS 8.) SUPPORT PVC CONDUITS ABOVE GRADE AS PER CODE.