Permit: T01CM04392

Parcel: 105131200

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/21/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL SUBJECT TO OTHER INSPECTORS.
07/17/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*HEAT STRIPS TO BE REMOVED.
07/11/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) #8 ROMEX CABLE ALLOW AMACITY IS 40 AMP PER CODE 336-26,310-15. ROOF OK.
07/10/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE USE AN APPROVED EXTENDER RING. OK TEMP POWER FOR TEST SUBJECT TO LAST INSPECTION OK POLE BASES (2).
07/03/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) COUNTER TOP RECEPTACLES TO BE OVER COUNTIER TOP NOT BEHIND REFRIDGERATOR 2. PLEASE INSTALL HOOD 3.) FINISH CUTTING OUT AROUND RECEPTACLE AND PROVIDE AN APPROVED EXTENDER RING AT GARBAGE DISPOSAL. 4.) FINISH WATER HEATER INSTALLATION. 5.) SUPPORT PVC CONDUITS ABOVE GRADE. 6.) SEALTITE FITTINGS ARE LOOSE AT A/C & DISCONNECT AND SUPPORT 7.) PLEASE LABEL DISCONNECT 8.) TIGHTEN CONNECTOR AT DISCONNECT 9.) FINISH OUTSIDE LIGHTING ASSOCIATE TO THIS BUILDING.