Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/21/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL SUBJECT TO OTHER INSPECTORS. |
| 07/17/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*HEAT STRIPS TO BE REMOVED. |
| 07/11/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) #8 ROMEX CABLE ALLOW AMACITY IS 40 AMP PER CODE 336-26,310-15. ROOF OK. |
| 07/10/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PLEASE USE AN APPROVED EXTENDER RING. OK TEMP POWER FOR TEST SUBJECT TO LAST INSPECTION OK POLE BASES (2). |
| 07/03/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) COUNTER TOP RECEPTACLES TO BE OVER COUNTIER TOP NOT BEHIND REFRIDGERATOR 2. PLEASE INSTALL HOOD 3.) FINISH CUTTING OUT AROUND RECEPTACLE AND PROVIDE AN APPROVED EXTENDER RING AT GARBAGE DISPOSAL. 4.) FINISH WATER HEATER INSTALLATION. 5.) SUPPORT PVC CONDUITS ABOVE GRADE. 6.) SEALTITE FITTINGS ARE LOOSE AT A/C & DISCONNECT AND SUPPORT 7.) PLEASE LABEL DISCONNECT 8.) TIGHTEN CONNECTOR AT DISCONNECT 9.) FINISH OUTSIDE LIGHTING ASSOCIATE TO THIS BUILDING. |