Permit: T01CM04391

Parcel: 105131200

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*PLEASE FILL UNUSED OPENING IN JUNCTION BOX BOTTOM.
07/17/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*TO HEAT STRIPS TO BE REMOVED. 2.) FINISH SITE LIGHTING AND OWNERS PANEL.
07/12/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*DISCONNECT FOR A/C HAVE BEEN CORRECTED AUX. HEAT STRIP TO BE REMOVED FOR OCCUPANCY FINISH LIGHTING FOR SITE. OK TEMP C OF O
07/11/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) #8 ROMEX CABLE ALLOWED AMPACITY IS 40 AMPS PER CODE 336-26,310-15. 2.) A/C UNIT 1101 HAS A WORKING CLEARENCE VIOLATION 110-26. 3.) FINISH OWNERS PANEL AND LIGHT FOR SITE.