Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/08/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*PLEASE FILL UNUSED OPENING IN JUNCTION BOX BOTTOM. |
| 07/17/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*TO HEAT STRIPS TO BE REMOVED. 2.) FINISH SITE LIGHTING AND OWNERS PANEL. |
| 07/12/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*DISCONNECT FOR A/C HAVE BEEN CORRECTED AUX. HEAT STRIP TO BE REMOVED FOR OCCUPANCY FINISH LIGHTING FOR SITE. OK TEMP C OF O |