Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/15/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 05/14/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) ROMEX WIRE MUST EXTEND INTO ELECTRIC BOXES AT LEASE 1/4" 2) HEADERS MUST BEAR ON TRIMMERS 3) FIRE BLOCK WEST KITCHEN ARCH |
| 05/08/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO WATER HEATER VENT 2) NO WATER HEATER T&P LINE 3) GROUND ALL METAL ELECTRIC BOXES 4) PROVIDE LADDER ACCESS TO CEILING JUNCTION BOXES |
| 05/01/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) YOU MUST REQUEST THRU IVR ALL DESIRED INSPECTIONS-IN FUTURE NO OTHER INSPECTION WILL BE MADE 2) GROUND ALL METAL ELECTRIC BOXES AND EXTENSIONS 3) NO GAS PRESSURE TEST-10 PSI MINIMUM REQUIRED 4) JOIST HANGERS REQUIRE DIAGONAL NAILS 5) FIRE BLOCK ALL DROP CEILINGS AND CHASES 6) GAS LINES NOT SUPPORTED PER UPC-1/2"-6', 3/4" 8', 1" AND LARGER 10' 7) NO WATER HEATER VENT OR T&P LINE 8) SJ CABLE NOT ALLOWED IN ATTIC 9) FIRE BLOCK FURRED WALLS 10) KITCHEN TRAP WEIR HIGHER THRU VENT OPENING 11) GALVANIZED CANNOT CONTACT COPPER 12) SD TO LOW 13) PROVIDE GROUNDS FOR ALL ELECTRIC SWITCHES AND OUTLETS |
| 02/12/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) MULTIPLE ITEMS NOT COMPLETE |