Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM04307

Parcel: 117050590


Addresses:

415 N 6TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM04307

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2002 ELECTRIC - FINAL Approved OK FINAL.
10/04/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
04/02/2002 ELECTRIC - FINAL Partial Approval 1.) PLEASE LABEL WATER HEATER IN BASEMENT AND PROVIDE WORKING CLEARENCES 2.)TIGHTEN SEAL TIGHT FITTINGS FOR COOLERS AND A/C'S ALSO PROTECT SEAL TIGHT WHERE IT PASSES THROUGH THE METAL HOLES 3.) FINISH #5 & #7. 4.) PLEASE PROVIDE GROUNDING FOR BOXES 250-148.OK TEMP C OF O SHOWER ROOMS OFFICES STUDIO UPSTAIRS SUBJECT TO BOND AND OTHER INSPECTION.
03/28/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*.1) PLEASE MOVIE A/C DISCONNECTS TO ALL FOR WORKING CLEARANCES ALSO LABELS. 2.) FINISH PHONE BOARD ROOM. 3.) BONDING JUMPER FOR BONDING THE PNAEL ENCLOSURE IS NEEDED 4.)PLEASE FILL ALL UNUSED OPENINGS FILL ER BLANK & KO SEALS 5.) THE PANELS NEED TO BE LABELED AND THE BREAKERS ALSO 6.) INTERIOR 200 A DISCONNECT NEED BONDING DEVICE AT CONCENTRICS ABOE 250 & 250-9. 7.) PLEASE REVISE PLANS TO REFLECT CHANGES IN SERVICE 8.) NEED TO BOND TO WATER OR BUILDNG STEEL FOR TRANSFORMER. 9.) PLEASE MOVE DATA SO AS TO ACCESS GUTTER COVER.