Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM04306
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
04/23/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) PLEASE REVISE PLANS TO REFLECT WORK INSTALLED 2.) CAN NOT RUN #8 SOLID IN A CONDUIT SYSTEM 310-3. 3.) DISCONNECTING MEANS FOR UNGROUNDED CONDUCTOR IS NEEDED PER CODE 225-31 & 225-32 ALSO SUPPLY IDENTIFICATION PER 225-37. 4.) WE HAVE AN OPEN SPLICE IN THE PULL BOX. 5.) PLEASE SUPPORT CONDUIT BETWEEN LIGHTS AS PER CODE 348-13. 6.) THE SUBPANEL IN OUTSIDE SHOP NEED TO BE LABELED AND WORKING CLEARENESS NEED TO BE MAINTAINED. PLEASE VERIFY PLANS THAT SHOW THAT PANEL AND PERMITTING FOR LOCATION. THERE IS NO SEAL OFF AND IT IS IN HARZARDOUS LOCATION. | |
11/13/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 1-3/4 PVC UNDERSLAB & PULL BOX. |