Permit: T01CM04303

Parcel: 107141010


Addresses:

2501 N FONTANA AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/15/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
11/14/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) NO WATER TEST ON PLUMBING 2) "S" STRAP NOT ALLOWED 3) NO PLANS ON SITE
11/13/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) SANITARY T FITTINGS NOT ALLOWED TO BE USED IN THE HORIZONTAL POSITION 2) 2 WAY CLEANOUT CANNOT BE USED AS A DRAIN FITTING 3) TRANSITION GLUE CANNOT BE USED ON TWO FITTINGS OF A.B.S. USE A.B.S. GLUE (BLACK) 4) SHORT RADIUS 1/4 BENDS NOT ALLOWED FOR HORIZONTAL CHARGE IN FLOW 5) TUB NOT VENTED