Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T01CM04251
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/27/2002 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection 0000*OK CONSTRUCTION POWER. | |
01/24/2002 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection 0000*1.) A SECOND GROUND ROD IS NEEDED 2.) YOU WILL NEED A BONDING DEVICE ON THE RISER 250-94 3.) PLEASE LABEL THE BREAKERS. | |
01/20/2002 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection 0000* | |
01/17/2002 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | IVRS - Inspection 0000*OK #1-4 SE CABLE 130' INTRENCH FOR TEMP POWER. OK #6-4 SE CABLE 100' IN TRENCH FOR TRAILER POWER. |