Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/18/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) ALL CORRECTIONS HAVE BEEN MADE 2.) PLBG FINAL IS OK 3.) OK FOR C OF O. |
| 12/13/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) WATER P & T DRAIN REQUIRED A UNION IN LINE 2.) MUST STRAP DISHWASHER DRAIN HOSE AS HIGH AS POSSIBLE TO BOTTOM OF COUNTER TOP WITH APPROVED STRAP. 3.) WATER CLOSETS MUST HAVE OPEN FRONT SEATS LESS LID ON COMMERCIAL BLDG. 4.) PROVIDE LISTING ON TWO HOLE STRAPS ON GAS LINE ON ROOF. 5.) CAN NOT HAVE TEE OR VALVE DOWNSTREAM OF BACKFLOW PREVENTER FOR CONNECTION OF IRRIGATION BACKFLOW. 6.) MSUT PROVIDE ADA WRAP FOR H.C. LAVATORY WASTE SUPPLY. 7.) LAVATORYS REQUIRE GRID STRAINERS NO POP UPS 8.) AS PER CONVERSATION WITH STEVE LONG LAVS COUNTER TOP HEIGHTS ARE OK. |