Permit: T01CM04184

Parcel: 132042730


Addresses:

3225 E 44TH ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/18/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
09/16/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0950*CORRECTIONS 1.) SOME FIXTURES ARE NOT PROPERLY FASTENED TO CEILING GRID. 2.) THE J-BOX ARE NOT PROPERLY FASTENED TO THE SUPPORT WIRE. THE WIRE IS NOT INSTALLED PER NE. CODE SEE ART 370,370-23 (D) & (I) AND 300-11. 3.) MARK THE AC AIR HANDLER DISCONNECT WITH THE SUPPLY LINE SIDE CIRCUIT #.
06/04/2002 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*