Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/18/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 09/16/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0950*CORRECTIONS 1.) SOME FIXTURES ARE NOT PROPERLY FASTENED TO CEILING GRID. 2.) THE J-BOX ARE NOT PROPERLY FASTENED TO THE SUPPORT WIRE. THE WIRE IS NOT INSTALLED PER NE. CODE SEE ART 370,370-23 (D) & (I) AND 300-11. 3.) MARK THE AC AIR HANDLER DISCONNECT WITH THE SUPPLY LINE SIDE CIRCUIT #. |
| 06/04/2002 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |