Permit: T01CM04177

Parcel: 112071740


Addresses:

2540 N TUCSON BL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/25/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) ABS DWV OK WATER TEST OK 2.) CONDENSATE RAN TO LAV. TAIL PIECE. 3.) WILL CALL FOR GAS INSPECTION 4.) OK TO COVER WALLS AND CEILING.
09/23/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) SUPPORT LAVATORY VENT.2.) YOU MAY NOT TIE-IN YOUR CONDENSATE DRAIN INTO THE VENT ABOVE THE BATHROOM 3.) WATER TEST ABS THROUGH ROOF. 4.) GET A PERMIT FOR GAS-YOU HAVE ADDED PIPING AT THE WATER HEATER. TEST TO 10#.
09/14/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) REDLINE "AS BUILTS" TO REFLECT INSTALLATION 2.) 3" ABS UNDERGROUND OK TIE-IN TO EXISTING OK TRANSITION FITTINGS OK 3.) ROUGH IN FOR NEW BATHROOM OK WATER TEST OK 4.) OK TO BACKFILL.