Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/17/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 10/16/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) CIELING COVER WITHOUT INSPECTION 2.) CK BOX CONDUCTOR FILL 370. 3.) MOVE ALL NM CABLE OUT OF CHANELS |
| 10/15/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0920*BLD LOCKED 920 CONTR. ON SITE. |
| 10/11/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 10/08/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*1.)POST PERMIT 2.) TYPE NM ROMEX TO BE PROTECTED BELOW 8" PANEL. 3.) PROVIDE BUSHED ENDS ON CONDUIT USED AS SLEEVES FOR ROMEX, 300-15C 300-16 N.E.C. 4.) ROMEX MUST HAVE 1 1/4: CLEARANCE FROM NAIL OR SCREWS WHEN RUN INSIDE CHANNEL OF METAL STUDS. 300-4 N.E.C. 5.) DISCONNECT SWITCHES OUTSIDE IN VIOLATION OF WORKING CLEARANCE 110-26 N.E.C. POOL EQUIPMENT. 6.) PROTECT CABLE FROM ABRAISION WHERE RUN ALONG EDGES OF FRAMING MEMBERS 300-15C N.E.C. |
| 10/03/2001 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*SYSTEM DOWN. |