Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM04150
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
10/16/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) CIELING COVER WITHOUT INSPECTION 2.) CK BOX CONDUCTOR FILL 370. 3.) MOVE ALL NM CABLE OUT OF CHANELS | |
10/15/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0920*BLD LOCKED 920 CONTR. ON SITE. | |
10/11/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
10/08/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*1.)POST PERMIT 2.) TYPE NM ROMEX TO BE PROTECTED BELOW 8" PANEL. 3.) PROVIDE BUSHED ENDS ON CONDUIT USED AS SLEEVES FOR ROMEX, 300-15C 300-16 N.E.C. 4.) ROMEX MUST HAVE 1 1/4: CLEARANCE FROM NAIL OR SCREWS WHEN RUN INSIDE CHANNEL OF METAL STUDS. 300-4 N.E.C. 5.) DISCONNECT SWITCHES OUTSIDE IN VIOLATION OF WORKING CLEARANCE 110-26 N.E.C. POOL EQUIPMENT. 6.) PROTECT CABLE FROM ABRAISION WHERE RUN ALONG EDGES OF FRAMING MEMBERS 300-15C N.E.C. | |
10/03/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*SYSTEM DOWN. |