Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/24/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) OK TO COVER WALLS. |