Permit: T01CM04088

Parcel: 13414001K

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM04088

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/28/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
09/27/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1999 NEC 110-112 MECHANICAL EXECUTION OF WORK, ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. 110-2 THE CONDUCTORS AND EQUIPMENT REQUIRED OR PERMITEED BY THIS CODE SHALL BE ACCEPTABLE ONLY IF APPROVED (THIS JURISDICTION DOES NOT APPROVED TIE WIRE AS THE ONLY MEANS OF SUPPORT FOR EMT CONDUIT.) 110-8 ONLY WIRING METHODS APPROVED BY THIS CODE ARE SUITABLE ( NO WHERE DOES THIS CODE STATE TIE WIRE SUITABLE.) 300-11 RACE WAYS SHALL BE SECURELY FASTENED IN PLACE 348-13 EMT SHALL BE SECURLY FOOTENED IN PLACE AT EVERY 10'AND WITH IN 3 & OF EACH BOX DEVICE CABINET. THIS JURISDICTION DOES NOT CONSIDER TIE WIRING DOWN AS A SECURING IN PLACE AND FASTENING TO METHOD.
09/25/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*NOTES 1.) SUPPORT RACEWAYS PER N.E.C.