Inspection History Details
Inspection Status: Closed
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM04087
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Closed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2007 | ELECTRIC - INTERMEDIATE | Closed | reference final approval 09/03 | |
07/28/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ RELEASE ON 480V, 2000A SW GEAR. WILL NEED A LETTER ON TORQUE ON GEAR AND GFI TEST ON 480V SW GEAR 250-94. THEN POWER WILL BE RELEASED. | |
06/09/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) NOTES: 1) OK GROUNDING AND MAKE UP 120/208 SWITCH GEAR, OK LAST INSPECTION WRITE-UP, PLEASE PROVIDE LETTER OF TORQUE FOR SWITCH GEAR | |
04/01/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* TEMPORARY FED NEW 600A 480V TRANSFER SWITCH & FEED TO NEW 600A MLD DISTRIBUTION PNL FEED TO NEW 150 KVA TRANS WHICH NEEDS LOVERS TO MAKE IT NEMA 12) FEED NEW 600A 120/208 DISCONNECT. NOTE 1. ALL EQUIPMENT NEEDS TO BE FULLY IDENTIFIED. 2.) TRANS NEEDS COVERS 3.) NOTE TRANS GROUND TEMPORARY TIED INTO EXISTING MCCD GROUNDING SYSTEM, WILL BE TRANFERRED TO MAIN GROUNDING GRID SYSTEM ONCE PERMANENT 120/208 SERVICE INSTALLED. BEFORE TRANSFER OF POWER FINISH ABOVE. |