Permit: T01CM04087

Parcel: 117200290


Addresses:

260 S CHURCH AV


Inspection Status: Closed

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM04087

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Closed

Date Description Inspector Results Comments
12/21/2007 ELECTRIC - INTERMEDIATE Closed reference final approval 09/03
07/28/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ RELEASE ON 480V, 2000A SW GEAR. WILL NEED A LETTER ON TORQUE ON GEAR AND GFI TEST ON 480V SW GEAR 250-94. THEN POWER WILL BE RELEASED.
06/09/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) NOTES: 1) OK GROUNDING AND MAKE UP 120/208 SWITCH GEAR, OK LAST INSPECTION WRITE-UP, PLEASE PROVIDE LETTER OF TORQUE FOR SWITCH GEAR
04/01/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
TEMPORARY FED NEW 600A 480V TRANSFER SWITCH & FEED TO NEW 600A MLD DISTRIBUTION PNL FEED TO NEW 150 KVA TRANS WHICH NEEDS LOVERS TO MAKE IT NEMA 12) FEED NEW 600A 120/208 DISCONNECT.
NOTE 1. ALL EQUIPMENT NEEDS TO BE FULLY IDENTIFIED.
2.) TRANS NEEDS COVERS
3.) NOTE TRANS GROUND TEMPORARY TIED INTO EXISTING MCCD GROUNDING SYSTEM, WILL BE TRANFERRED TO MAIN GROUNDING GRID SYSTEM ONCE PERMANENT 120/208 SERVICE INSTALLED. BEFORE TRANSFER OF POWER FINISH ABOVE.