Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM04077

Parcel: 111050580


Addresses:

3617 E PRESIDIO RD

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/06/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
10/18/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) UNDERGROUND NON METALIC CONDUIT MUST BE 18" BELOW GRADE OR BELOW 2" CONCRETE 2) ELECTRIC SUB PANEL MUST HAVE AN ISOLATION NEUTRAL BAR, ALL OTHER ELECTRIC BUT ITEMS 1 AND 2 ARE OK
09/04/2001 BUILDING - FINAL Denied IVRS - Inspection 0950*NOTE: YOU MUST CALL IN ALL REQUIRED INSPECTION 1. BUILDING IS NOT SIZED PER PLAN WEST SET BACK PER PLAN IS 15 FEET ACTUAL IS 20 FT REUSE PLAN & HAVE APPROVED BY CITY OF TUCSON 2.) PROVIDE PROOF OF BUILDING FOUNDATION. 3.) EXPOSE UNDERGROUND ELECTRIC SERVICE AT EACH END OF RUN. 4.) PROVIDE PROOF LOAD CALCAULATIONS FOR MAIN AND SUB ELECTRIC SERVICE PANEL. APPROVED BY CITY OF TUCSON 5.) OVERSIZE CONDUCTORS CANNOT BE TRIMMED TO FIT" AT MAIN ELECTRIC SERVICE. 6.) PROVIDE ACCESS TO ELECTRICAL SUB PANEL. REQUIRED 30 X 30 WORK AREA IN FRONT OF PANEL 7.) BUILDING IS METAL REQUIRED BONDING 8.) BUILDING IS FLAT ROOFED WITH NO PITCH HEIGHT 10' - 0" REVISE PLAN & HAVE APPROVED. 9.) BUILDING IS NOT CONSTRUCTED OR ANCHORED PER PLAN. BUILD TO PLAN OR REVISE PLAN TO AS BUILT AND HAVE APPROVED BY CITY OF TUCSON STOPPED INSPECTION.