Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM04067
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
10/23/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) SOME ELECTRICAL HOME RUNS WERE HIT BY STAPLES FROM OUTSIDE WHERE INSULATION ON CONDUCTOR IS CUT, MUST BE REPLACED 2) NO WATER TEST 3) NO TEST DWV SYSTEM 4) ELECTRIC RISER NOT INSTALLED |