Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/07/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) BLDG. DRAIN IS STUBBED OUT OF BLDG @ 2 WAY C.O. ONLY. 3.) YARD WATER LINE FROM METER TO BLDG SERVICE IS OK 4.) OK TO BACKFILL TRENCH. |
| 12/27/2001 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) ROUGH PLBG. SYSTEM HAS BEEN FLAT VENTED BY PLBG. CONTRACTOR. THERE IS NO STRUCTURE CONDITION THAT WILL NOT ALLOW SYSTEM TO BE ROUGHED IN CONVENTIONLY. SEE SECTION: 905.3 94 UPC. 2.) MUST PROVIDE A 0FT HEAD OF WATER TEST. SEC SECTION: 712.2 94 UPC. |