Permit: T01CM04032

Parcel: 112062800


Addresses:

2420 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM04032

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/24/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) HIGH LEG OF 240VOLT 4 WIRE SYSTEM TO BE COLOR CODED ORANGE PER NEC AND #9287 CITY OF TUCSON ORDIN.
04/23/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0920*BLD LOCKED, RE CALL INSP. WHEN ACCESS AVAILABLE, DUE TO WORK LOAD CANNOT RETURN TODAY. UNLESS AFTER HOURS REQUEST.
03/12/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) PANEL INDEX NEEDS CORRECT INFO. 2.) PANELS "SP" & R' REQUIRE MAIN CB PER PLAN SHEET E4-ONE LINE POWER DIST. SCHEMATIC 3. RED LINE PLANS SUBMIT FOR APPROVAL OF REVISIONS CORRECT & RECALL.4.) IDENTIFY EXTERIOR SWITCH DISCONNECT WITH THE PANEL THEY SERVE
03/07/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* OK TO CLEAR TEMP POWER PLUMBING IS FINALED MECH. IS FINALED NOTIFIED ART M.