Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T01CM04032

Parcel: 112062800


Addresses:

2420 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/26/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/24/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) HIGH LEG OF 240VOLT 4 WIRE SYSTEM TO BE COLOR CODED ORANGE PER NEC AND #9287 CITY OF TUCSON ORDIN.
04/23/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0920*BLD LOCKED, RE CALL INSP. WHEN ACCESS AVAILABLE, DUE TO WORK LOAD CANNOT RETURN TODAY. UNLESS AFTER HOURS REQUEST.
03/12/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) PANEL INDEX NEEDS CORRECT INFO. 2.) PANELS "SP" & R' REQUIRE MAIN CB PER PLAN SHEET E4-ONE LINE POWER DIST. SCHEMATIC 3. RED LINE PLANS SUBMIT FOR APPROVAL OF REVISIONS CORRECT & RECALL.4.) IDENTIFY EXTERIOR SWITCH DISCONNECT WITH THE PANEL THEY SERVE
03/07/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* OK TO CLEAR TEMP POWER PLUMBING IS FINALED MECH. IS FINALED NOTIFIED ART M.