Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM04032
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/24/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) HIGH LEG OF 240VOLT 4 WIRE SYSTEM TO BE COLOR CODED ORANGE PER NEC AND #9287 CITY OF TUCSON ORDIN. | |
| 04/23/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*BLD LOCKED, RE CALL INSP. WHEN ACCESS AVAILABLE, DUE TO WORK LOAD CANNOT RETURN TODAY. UNLESS AFTER HOURS REQUEST. | |
| 03/12/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) PANEL INDEX NEEDS CORRECT INFO. 2.) PANELS "SP" & R' REQUIRE MAIN CB PER PLAN SHEET E4-ONE LINE POWER DIST. SCHEMATIC 3. RED LINE PLANS SUBMIT FOR APPROVAL OF REVISIONS CORRECT & RECALL.4.) IDENTIFY EXTERIOR SWITCH DISCONNECT WITH THE PANEL THEY SERVE | |
| 03/07/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TO CLEAR TEMP POWER PLUMBING IS FINALED MECH. IS FINALED NOTIFIED ART M. |