Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 11/02/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) SUPPORT CONDUIT PER 348-13 N.E.C 2.) CONDUIT NOT TO TOUCH COPPER WATER LINES WITHOUT AN INSULATING MATERIAL BETWEEN. 3.) USE BOX OFFSETS ON PIPE BENDS SO AS NOT TO BIND CONDUIT AT SUPPORTS, CONDUITS MUST LAY FLAT ON STRUCTURE AT SUPPORTS WHEN USING 1HOLE STRAPS 110-12 348 NEC. |
| 10/08/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245* |