Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM04019
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
10/29/2001 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) NEED PLUMBING LINES TESTED | |
10/25/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) STUDS MISSING AT CLOSET WALL TO HALL BATH 2) COULD NOT CHECK REST OF HOUSE FOR MISSING ANCHOR BOLTS, HOUSE IS INSULATED WITH BLOWN INSULATION-LOOSE FILL FIBERGLASS 3) MOISTURE BARRIER INSTALLED AT CEILING 4) COULD NOT CHECK REST OF HOUSE DO TO FLYING INSULATION, STARTED ITHCING | |
10/24/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) MISSING HANGERS AT GARAGE HIPS 2) MISSING ANCHOR BOLTS 3) NO GAS TEST 4) PLUMBING NOT COMPLETE AT BATH 5) CHECK FOR MISSING FIREBLOCKING 6) NEED WATER TEST 7) USE #10D NAILS AT HANGERS |