Permit: T01CM04014

Parcel: 141147440

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/10/2001 FRAMING Approved IVRS - Inspection 0000*
12/06/2001 FRAMING Denied IVRS - Inspection 0935*/ 1) A RE-FEE HAS BEEN ASSESED FOR THIS INSPECTION, MULTIPLE INSPECTIONS HAVE BEEN MADE WITH NO PROGRESS ON JOB SITE, PLEASE PAY THIS RE-FEE AT 201 N STONE AVE SO THAT INSEPCTIONS CAN CONTINUE 1) PROTECT ELECTRICAL AT GARAGE RIGHT SIDE OF FURNACE AREA WITHIN 1 1/4 FROM EDGE OF STUD 2) HTT AT GARAGE WALL NOT TIGHTENED 3) FLAPPER FOR EXHAUST FAN IN LAUNDRY ROOM MISSING 4) NEED 1" CLEARANCE MINIMUM COMBUSTIBLES AT FURNACE FLUE
12/04/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) 11/30 FAILURE NOT CORRECTED (MINIMUM 6" CLEARANCE) A RE-INSPECTION FEE WILL BE IMPOSED IF THIS INSPECTION FAILS AGAIN
11/30/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) NUMBER 1 FROM PREVIOUS INSPECTION NOT DONE
11/21/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) MOVE PEX FROM FLUE ABOVE PLENUM 2) TIGHTEN H.D. AT REAR GARAGE WALL 3) CORRECT DUCT WORK ABOVE LAUNDRY 4) REFRAME WALL AT DRYER VENT VERTICLE 5) CORRECT DRYER VENT RUN 6) DETERMINE WATER LEAK AND REPAIR
11/20/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*
11/16/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*