Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 03/25/2004 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 03/22/2004 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED CITY APPROVED REVISION: NEED TO KNOW IF IT REQUIRES 3 SEPERATE RUNS FROM METER CAN TO EACH OF 3 INDIVIDUAL DISCONNECT 2) ACCURATELY REFLECT WIRE SIZES TO ALL 3 DISCONNECTS 3) NEED MAIN BOND JUMPER TO EACH NEUTRAL BAR AT EACH DISCONNECT |
| 03/18/2004 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245*/ 1) BOND UFER PER PLAN 2) BOND BUSHING REQUIRED ON BOTH ENDS OF NIPPLES AT SERVICE 3) USE CORRECT GROUND WIRE SIZE FOR BOND BUSHINGS 4) LABEL DISCONNECTS, PANELS, PANEL SCHEDULES, INSTALL ADDRESS LABEL ON SERVICE ENCLOSURE 5) INSTALL FUSES AND REJECTION PINS 6) SCRAP OFF ENAMEL UNDER GROUND LUGS |