Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2003 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 08/18AM |
| 08/11/2003 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) DRIVE 2-8' GROUND RODS MINIMUM 6' APART 2) INSTALL #4 BARE COPPER GROUNDING ELECTRODE CONDUCTOR (UNSPLICED) CONNECTING 2 GROUND RODS AND TERMINATING IN MAIN PANEL ON GROUNDING BUS BAR 3) USE APPROVED CLAMPS AT CONNECTIONS |
| 08/05/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*/ 1) UFER GROUND NOT CONNECTED 2) NO GFCI FOR TEMP SERVICE |