Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date |
Description |
Inspector |
Results |
Comments |
| 06/13/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Approved |
IVRS - Inspection 0000* |
| 06/11/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Denied |
IVRS - Inspection 0999*/ 1) REINFORCING STEEL FOR BOND BEAM MUST BE A MINIMUM OF 1 1/2" BELOW TOP OF BLOCK |
| 05/23/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) 1ST LIFT 4' HIGH-OK |
| 05/15/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) COMPLETE #1, 2, AND 3 ABOVE RECALL WHEN READY |
| 03/28/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/28/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) LAY BLOCK WALLS TO 48" HEIGHTH 2) INSTALL VERTICAL REBAR 3) RECALL BEFORE GROUTING |