Permit: T01CM03996

Parcel: 12107462C


Addresses:

5920 E PIMA ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM03996

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
01/28/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O.
1.) RECEIVED LETTER FOR WORK TO TAKE CARE OF WORKING CLEARENCES INFRONT OF SERVICE. FINAL WILL BE ON COMPLETION OF WORK AS PER LETTER.
01/27/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FINISH PREVIOUS INSPECTION.
01/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) MAINTAIN WORKING CLEARENCES IN FRONT OF SERVICE.
2.) A PERMANENT METAL LABEL IS NEEDED TO ADDRESS SERVICE.
3.) CABLE BRACING IS NEEDED FOR SERVICE LATERALS PER MANUFACTURES.
4.) PLEASE LABELS AS PER 110-22 FOR SERIES RATING.
5.) PLEASE PROVIDE A LETTER VERIFYING TORQUE VALUES FOR SERVICE SECTION.
6.) FINISH TERMANATION OF CIRCUITS.