Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/28/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 11/19/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) WORKING CLEARENCE IN FRONT OF W/H DISCONNECT. 2.)NEED REVISED PLANS FOR SERVICE APPROVED BY CITY OR INSTALL AS PER PLANS. |
| 11/16/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) NEED EXIT LIGHTS 2.) NEED DISCONNECTING MEANS FOR WATER HEATER 3.) FILL UNUSED OPENING IN PANEL 4.) LABEL PANELS ON OUTSIDE COVER 5.) BOND ENCLOUSER 6.) NEED SERVICE REVISION APPROVED BY CITY OR INSTALL AS PER PLAN. |