Permit: T01CM03960

Parcel: 138233510


Addresses:

931 W ACADIA DR

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
09/06/2001 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection 0000*
09/04/2001 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection 0999*1.) PROVIDE 40 TIMES DIA. OF REBAR @ CORNERS. 2.) PROVIDE 3" MIN. PACE FROM GROUND. HAVE PLANS & PERMITES @ SITE.
08/29/2001 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection 0999*/ 1) REBAR IN GROUND NEEDS TO BE ISOLATED AT HORIZONTAL REBAR CONNECTION 2) PROVIDE 40 XS DRAMETER OF BAR OVER LAPS 3) #3 INSTALLED THRU-OUT REVISE PLAN FOR AS BUILT VERTICAL BARS NOT INSTALLED PROPER ALSO EMBEDDED IN EARTH NOT PROVIDING VERTICAL LAP LENGTH