Permit: T01CM03956

Parcel: 132150020


Addresses:

815 E AJO WY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM03956

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/04/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) ALL WIRING TO BE ABOVE 20" AFG 2.) 30A WP OUTLET MISSING FOR MOTOR. 3.) THE MOTOR WIRING TO BE 20" AFG. 4.) MOTOR NOT RATED TO IN 20" OR BELOW AREA. 5.) SW RELAY WIRING TO INTERUP NOT RATHER THAN NEUTRAL 6.) LABEL MOTOR CIRCUIT ON PNL A SCHEDULE.
10/31/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) SEALTIGHT FITTING GOING INTO SOLDENDID CONTROL PANEL WITH CIRCUIT 7 LOOSE 2.) CIR A-1 30AMP TO FEED A 30A WP RECETACLE NEXT TO PANEL A? 3.) NEED TO VERIFY 1/2 HP SUBMERSIBLE PUMP AS CLASS DIVI. 4.) APPEARS THE WIRING METHOD TO SOLENOD ACTIVATED VALVE IS USING A WATER FITTING IN ITS MAKE UP. 5.) THE SUPPOR FOR THE SEALTIGHT NON METELLIC NOT PROPERLY SUPPORTED HANGING IN FREE AIR. 6.) WILL NEED TO INSPECT SUE UNIT CONTROL BOX TO CHECK TERMINATIONS AND LISTING DID NOT ANT TO OVEN WHILE RUNNING SHOWING 80A BKR NOT TOP ATTEMP TO SET UP MEETING WITH INSTALLER AND MYSELF FOR ON SITE INSPECTION CALL RAY MAJUTA AT OFFICE M-F 7-9AM. OR CELL 909-5184 TO SET UP MEETING.
10/30/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
10/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0920*LOCKED PLEASE RECALL
08/27/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*THIS IS NOT WIRED PER APPROVED PLAN. CONDUIT SIZER FEEDER ORIGINATION DISCONNECTS PER PLAN ON EQUIPMENT SEAL OFF REQUIREMENT AT 20" AFG PER PLAN.