Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM03909
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
10/25/2001 | FRAMING | Not ready for Inspection | 1) STIFF LEG 2 X 4 FRONT PORCH CEILING 2) ADD SUPPORT BLOCKS PROCH BEARING NORTH BATH ROOF ( PLATE BEARING ON OSB ONLY 3) MOVE (A.C. AND ROMEX LINES AWAY FROM LIGHT CAN KITCHEN CEILING 4) "B" TRUSSES ARE 3 PT. BEARING AND REQUIRE A RAT RUN, MID/PT. 3-14 JOINTS 5) S, A1 TRUSSES ARE 3 POINT BEARING NEED SHIMS AND RAT RUNS SEE TRUSS SHEAR DRAWINGS 6) INSIDE WALL GARAGE, SHEAR TRANSFER, UP TO MAIN DOOR AT SHIM BETWEEN TOP PLATE AND TRUSS CHORD ANDD 43.5'S 6) GAS TEST OK |