Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01CM03889
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2001 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*OK TO CLEAR. | |
| 12/06/2001 | ELECTRIC - CABLE DROP | Denied | THE GROUND WIRES ARE IRRIVERIBLY DAMAGED. BUTT SPLICE A SOLID WIRE OF EQUIVELANT AMPERAGE TO THE STRANDED GROUNDS AND RETERMINATE. CUT BACK THE STRANDED WIRE TO A POINT WHERE ALL THE CONDUCTORS WILL BE INCLUDED IN THE CRIMP SLEEVE. MUST BE CRIMPED. LEAVE COVERS OFF FOR INSPECTION. | |
| 12/03/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0950* | |
| 12/03/2001 | ELECTRIC - CABLE DROP | Not ready for Inspection | ||
| 11/30/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0225*1.) THE "UFER" MUST BE LANDED ON THE NEUTRAL BAR. 2.) RUN BONDING WIRE FROM GROUND BAR TO BONDING BUSHING. 3.) THE NEUTRAL IS FACTORY BONDED TO THE CAN W/ TWO BLACK SCREWS, TEP SIDE. 4.) SCRAPE PAINT OFF CAN UNDER GROUND BAR. CORRECT & RECALL 5.) CRIMP SOLID WIRE TO DAMAGED GROUND WIRES AND RECONNECT. THE STRANDS HAVE BEEN CUT OFF AND THE WIRE UNWOUND. |