Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 12/11/2001 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 12/06/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
THE GROUND WIRES ARE IRRIVERIBLY DAMAGED. BUTT SPLICE A SOLID WIRE OF EQUIVELANT AMPERAGE TO THE STRANDED GROUNDS AND RETERMINATE. CUT BACK THE STRANDED WIRE TO A POINT WHERE ALL THE CONDUCTORS WILL BE INCLUDED IN THE CRIMP SLEEVE. MUST BE CRIMPED. LEAVE COVERS OFF FOR INSPECTION. |
| 12/03/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0950* |
| 12/03/2001 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
|
| 11/30/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0225*1.) THE "UFER" MUST BE LANDED ON THE NEUTRAL BAR. 2.) RUN BONDING WIRE FROM GROUND BAR TO BONDING BUSHING. 3.) THE NEUTRAL IS FACTORY BONDED TO THE CAN W/ TWO BLACK SCREWS, TEP SIDE. 4.) SCRAPE PAINT OFF CAN UNDER GROUND BAR. CORRECT & RECALL 5.) CRIMP SOLID WIRE TO DAMAGED GROUND WIRES AND RECONNECT. THE STRANDS HAVE BEEN CUT OFF AND THE WIRE UNWOUND. |