Permit: T01CM03889

Parcel: 134082840

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01CM03889

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2001 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*OK TO CLEAR.
12/06/2001 ELECTRIC - CABLE DROP Denied THE GROUND WIRES ARE IRRIVERIBLY DAMAGED. BUTT SPLICE A SOLID WIRE OF EQUIVELANT AMPERAGE TO THE STRANDED GROUNDS AND RETERMINATE. CUT BACK THE STRANDED WIRE TO A POINT WHERE ALL THE CONDUCTORS WILL BE INCLUDED IN THE CRIMP SLEEVE. MUST BE CRIMPED. LEAVE COVERS OFF FOR INSPECTION.
12/03/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0950*
12/03/2001 ELECTRIC - CABLE DROP Not ready for Inspection
11/30/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0225*1.) THE "UFER" MUST BE LANDED ON THE NEUTRAL BAR. 2.) RUN BONDING WIRE FROM GROUND BAR TO BONDING BUSHING. 3.) THE NEUTRAL IS FACTORY BONDED TO THE CAN W/ TWO BLACK SCREWS, TEP SIDE. 4.) SCRAPE PAINT OFF CAN UNDER GROUND BAR. CORRECT & RECALL 5.) CRIMP SOLID WIRE TO DAMAGED GROUND WIRES AND RECONNECT. THE STRANDS HAVE BEEN CUT OFF AND THE WIRE UNWOUND.