Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/01/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/30/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*BOND JUMPER FROM UFER TO NEUTRAL BUS. 2.) BOND TO BLD STEEL NOT TO WRAP AROUND BOLT NEEDS LUG & BOLT. (#10 LARGEST TO WRAP AROUND.) 3.) STRAP RISERS AT SERVICES. |
| 09/12/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) INSTALL PERMANENT ADDRESS LABELS FOR EACH METER. 2.) INSTALL BOND SCREW OR BOND JUMPER AT SUB-PANEL TO BOND NEWTRAL. NO EQUIP GROUND RUN WITH FEEDERS. 3.) SHEET METAL SCREW NOT ALLOWED TO ATTACH MECH. LUGS FOR SERVICE GROUNDING SCRAP OFF ENAMEL PAINT. 250-8. 250-12 110-12 NEC. 4.) I.D. CIRCUIT BREAKERS IN SUB-PANEL. 5.) NEED REVISION FROM ARCH. FOR DELETION OF FLOURESCENT LIGHT FIXTURES & ELECTRIC GATE OPENER. 6.) BOND BLD STEEL TO SERVICE GRNDING ELECTRODE CONDUCTOR. |