Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/06/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 06/05/2002 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 06/03/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0935*/ 1) A REFEE HAS BEEN ASSES 2) CALLED 808-1288, 4 TIMES NO ANSWER |
| 05/31/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO ADDRESS POSTED 2) CAP CLEAN-OUT WEST WALL 3) SEAL STUCCO HOLES FRONT ENTRY 4) SEAL KNOCKOUT AT BOTTOM ELECTRIC PANEL 5) MANN DOORR AT GARAGE NOT SELF CLOSING 6) PROVIDE ACCESS DOOR FOR JACUZZI 7) SEAL GAS LINE AT FIREPLACE WITH FIRE CAULK 8) SEAL PENETRATION BEARING STOVE AT GAS LINE 9) MOVE DIRT AWAY FROM HOUSE 10) PAINT ALL PVC VENTS AT ROOF 11) PROVIDE POSITIVE FLOW FOR CONDENSATE LINE 12) PROVIDE PROPER FUSES AT A/C DISCONNECT PER MANUFACTURERS INSTRUCTIONS 13) UNION NOT ALLOWED BEFORE GAS SHUT OFF VALVE |
| 05/28/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO PLANS PERMIT ON SITE 2) NEXT FAILURE WILL RESULT IN A RE-FEE 3) HOUSE LOCKED |
| 05/21/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0920* |
| 05/10/2002 |
BUILDING - FINAL |
|
Cancelled |
IVRS - Ri canceled |