Permit: T01CM03869

Parcel: 120010740

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM03869

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2001 FRAMING Approved IVRS - Inspection 0000*
09/21/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) SECURE WATER VALVE AT SHOWER 2) ISOLATE UPPER AND LOWER COMBUSTIBLE AIR AT GARAGE 3) BLOCK VENTS AT 3 SIDES
09/19/2001 FRAMING Denied IVRS - Inspection 0222*/ 1) BLOCK AROUND MECHANICAL DUCTS 2) SECURE 4 GANG BOX 3) PROVIDE 50 PSI MINIMUM AIR TEST TO WATER LINES 4) ISOLATE UPPER AND LOWER COMB AIR IN GARAGE 5) FHA STRAP DOUBLE TOP PLATE AT CONDENSATION LINES AND GAS LINE 6) PROVIDE KING STUDS AT MASTER BEDROOM WINDOW