Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) GAS ON PRESSURE TEST NOT NECESSARY 2.) ALL CORRECTIONS MADE OK 3.) PLUMBING FINAL OK. |
| 11/26/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*A.) PERMIT IS FOR GENERAL REPAIRS 1. GAS IS ON, HOWEVER -GAS VALVES ARE NOT APPROVED. 2.) I WANT TO SEE A 10# TEST ON GAS SYSTEM. 3.) INSTALL 3 SCREWS WHERE APPLIANCE CONNECTOR MEETS VENT CONNECTOR. USE METAL TAPE ON ALL VENT CONNECTOR JOINTS. DO NOT TAPE DOUBLE WALL CONNECTION.4.) REQUIRED ONE INCH CLEARANCE AROUND VENT PASSING THRU COMBUSTIBLES. |
| 11/20/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |