Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/10/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 05/17/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/06/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK BONDING JUMPERS ON MAIN FEEDERS OK TERMINATION FOR MAIN FEEDERS. |
| 05/03/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) CONDUIT RUNS NOT TO HAVE MORE THAN 360 IN A RUN. 2.) BONDING JUMPER TO BE SIZED PER 250-102. 3.) PLEASE PROVIDE A LETTER ON COMPANY LETTERHEAD VERIFING TORQUE VALVES. LEFT PAPERWORK FOR TEMP POWER & TEMP C OF O. |
| 04/23/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* OK STORAGE ROOMS 1ST FLOOR. |
| 04/10/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
OK WALLS AND HARD CEILINGS 2ND FLOOR OFFICES. |
| 04/03/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK CENTER WALL ABOVE BRICK. OK WALLS OFFICES 1ST FLOOR ONLY. |
| 04/02/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK CENTER NORTH FIRE WALL ABOVE BLOCK IN PARTS ROOM 2.) WE HAVE LOOSE FITTINGS AND LOCK NUTS PLEASE TIGHTEN. |
| 04/01/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK CONDUIT IN NORTH FIRE WALL ABOVE BLOCK. |
| 03/19/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* OK 2ND LIFT CENTER WALL. |
| 03/03/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK 2-1" & 1 3/4" PVC FOR LIGHTING UNDER PARKING LOT. |
| 02/26/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK 1-3/4" RIDGID BELOW SLAB IN CLASSIFIED AREA OK 1-4" PRIMARY ELECTRIC. |
| 02/25/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK 2-4" PVC FEEDERS 1.) PVC CONDUIT LOCATED IN HAZARDIOUS LOCATION NEED TO BE AT 2' DEPTH PER EXCEPTION 511-4. |
| 02/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
|
| 02/20/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL AT SERVICE 4-2" PVC PANEL FEEDS 2 -1 1/2 1-1" INTO BLDG. PLEASE OPEN 2010 IN SCREEN. |
| 02/15/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK 2ND & 3RD LIFT OFFICES OK 4-2 PVC SES TO IN BUILDING OK 2-1 1/4 & 1 1" PVC 90 STUBS OK 1-1" PVC FROM LIGHT POLE BY TASH AREA TO WEST END POLE ALONG THE BACK OF THE BUILDING. |
| 02/12/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) ALL UNDERGROUND CONDUIT TO BE EXPOSED FOR INSPECTION WE HAVE NOT SEEN ANY OF THE RUNS AS OF THIS TIME. OK 1ST LIFT INTERIOR OFFICE WALLS OK 4-2" RIDGID 90 TO OUTSIDE. OK 8-3/4" RIGID 90 TO OUTSIDE. |