Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM03860
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
05/17/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
05/06/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK BONDING JUMPERS ON MAIN FEEDERS OK TERMINATION FOR MAIN FEEDERS. | |
05/03/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) CONDUIT RUNS NOT TO HAVE MORE THAN 360 IN A RUN. 2.) BONDING JUMPER TO BE SIZED PER 250-102. 3.) PLEASE PROVIDE A LETTER ON COMPANY LETTERHEAD VERIFING TORQUE VALVES. LEFT PAPERWORK FOR TEMP POWER & TEMP C OF O. | |
04/23/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK STORAGE ROOMS 1ST FLOOR. | |
04/10/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALLS AND HARD CEILINGS 2ND FLOOR OFFICES. | |
04/03/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK CENTER WALL ABOVE BRICK. OK WALLS OFFICES 1ST FLOOR ONLY. | |
04/02/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK CENTER NORTH FIRE WALL ABOVE BLOCK IN PARTS ROOM 2.) WE HAVE LOOSE FITTINGS AND LOCK NUTS PLEASE TIGHTEN. | |
04/01/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK CONDUIT IN NORTH FIRE WALL ABOVE BLOCK. | |
03/19/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK 2ND LIFT CENTER WALL. | |
03/03/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 2-1" & 1 3/4" PVC FOR LIGHTING UNDER PARKING LOT. | |
02/26/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 1-3/4" RIDGID BELOW SLAB IN CLASSIFIED AREA OK 1-4" PRIMARY ELECTRIC. | |
02/25/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 2-4" PVC FEEDERS 1.) PVC CONDUIT LOCATED IN HAZARDIOUS LOCATION NEED TO BE AT 2' DEPTH PER EXCEPTION 511-4. | |
02/22/2002 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | ||
02/20/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PARTIAL AT SERVICE 4-2" PVC PANEL FEEDS 2 -1 1/2 1-1" INTO BLDG. PLEASE OPEN 2010 IN SCREEN. | |
02/15/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 2ND & 3RD LIFT OFFICES OK 4-2 PVC SES TO IN BUILDING OK 2-1 1/4 & 1 1" PVC 90 STUBS OK 1-1" PVC FROM LIGHT POLE BY TASH AREA TO WEST END POLE ALONG THE BACK OF THE BUILDING. | |
02/12/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) ALL UNDERGROUND CONDUIT TO BE EXPOSED FOR INSPECTION WE HAVE NOT SEEN ANY OF THE RUNS AS OF THIS TIME. OK 1ST LIFT INTERIOR OFFICE WALLS OK 4-2" RIDGID 90 TO OUTSIDE. OK 8-3/4" RIGID 90 TO OUTSIDE. |