Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T01CM03859
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2003 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection 0000* | |
| 07/16/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*TEST TO M.H. OK WILL NEED VARIFICTION OF GRADE & ALL CO TO GRADE ON SEWER. | |
| 07/08/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*REVISED PLAN APPROVED AS OF 6/5/02. TEST ON SITE SEWER IT BRANCHES OK AT THIS TIME. OK TO BACKFILL SUBJECT TO VARIFICATION OF GRADE. PROVIDE ACCESS TO BACKWATER VALVE INSTALL CO AT SAND & OIL TANK. | |
| 07/03/2002 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000*FIX JOINTS #17-33 LEAK. | |
| 06/28/2002 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000*NO TEST. | |
| 06/27/2002 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000* | |
| 06/26/2002 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000*NO APPROVED REVISED PLAN ON JOB FOR SITE SEWER PLEASE PROVIDE APPROVED STAMP ON JOB AT TIME OF NEXT INSP. | |
| 05/30/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*SAND & SOIL ONLY. | |
| 05/09/2002 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000* ALTERNATE MATERIALS AND METHODE APPEAL TO THE BUILDING OFFICAL FOR DESIGN AND ALTERNATE MATERIALS FOR SPECIAL CONDITIONS THAT OUR NOT LISTED IN THIS CODE. PLEASE PROVIDE APPROVED APPEAL AT TIME OF NEXT INSP PLEASE PROVIDE APPROVED REVISED PLANS AS NEEDED. | |
| 05/08/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*94 UPC 708.0 4" OR HANGER NOT LESS THEN 1/8 INCH PER. FOOT ON 1 PERCENT. SEE PIMA COUNTY 4.4 % 6" OR LARGER STATE 4.0%. SIZE OF WASTE LINE NOT ON PLAN WEST SIDE OF BLDG. & SOUTH SIDE OF BLDG. SITE PLAN PLUMBING FLOOR PLANS CALLS FOR 4" NO SPEC ON PIPE PLEASE PROVIDE REVISED PLAN VARIFICATION OF GRADE CONTRACTOR WILL TEST AT LATER DATE. | |
| 03/14/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000* APROX 52' 8" SDR 35 FROM M-H PLEASE PROVIDE VARIFICATION IF GRADE CONTRACTOR WALL PROVIDE AIR TEST AT LATER DATE. | |
| 03/13/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*M-H IN STREET 13'O" INSTALLED OK TO BACKFILL WILL REQUIRE VARIFICATION OF GRADE CONTRACTOR WILL AIR TEST AT LATER DATE. |