Permit: T01CM03850

Parcel: 136308250

Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Permit Number - T01CM03850

Inspection Description - BUILDING PRE-SLAB

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2001 BUILDING PRE-SLAB Approved IVRS - Inspection 0000*
09/21/2001 BUILDING PRE-SLAB Denied IVRS - Inspection 0999*/ 1) FORMS NOT LEVEL 2) FF WILL NOT BE THE SAME AS EXISTING 3) FORMS ARE LOWER THAN GROUND AT SOUTH END, WILL NEED TO MAINTAIN 6" FROM WOOD (BOTTOM PLATE) 4) NEED 3" CLEARANCE BETWEEN EARTH AND STEEL 5) NO ANSWER AT DOOR
09/18/2001 BUILDING PRE-SLAB Denied IVRS - Inspection 0999*/ 1) FORMS APPEAR OUT OF SQUARE AND OUT OF LEVEL 2) FORMS SET AT BOTTOM OF STUCCO WHICH IS 1" BELOW EXISTING FLOOR LEVEL? 3) MAINTAIN MINIMUM 3" CLEARANCE REBAR TO DIRT 4) SUPPORT VERTICAL REBAR IN PLACE 5) NO ANSWER AT DOOR 6) NO PLANS VISIBLE 7) RECALL AFTER ABOVE CORRECTED
09/17/2001 BUILDING PRE-SLAB Denied IVRS - Inspection 0999*/ 1) PROVIDE MINIMUM OF 3" CLEARANCE AT REBAR FROM ENTRY 2) OVER LAP SHOULD BE 40 TIMES DIAMETER OF REBAR
09/11/2001 BUILDING PRE-SLAB Not ready for Inspection