Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T01CM03850
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2001 | BUILDING PRE-SLAB | Approved | IVRS - Inspection 0000* | |
09/21/2001 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*/ 1) FORMS NOT LEVEL 2) FF WILL NOT BE THE SAME AS EXISTING 3) FORMS ARE LOWER THAN GROUND AT SOUTH END, WILL NEED TO MAINTAIN 6" FROM WOOD (BOTTOM PLATE) 4) NEED 3" CLEARANCE BETWEEN EARTH AND STEEL 5) NO ANSWER AT DOOR | |
09/18/2001 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*/ 1) FORMS APPEAR OUT OF SQUARE AND OUT OF LEVEL 2) FORMS SET AT BOTTOM OF STUCCO WHICH IS 1" BELOW EXISTING FLOOR LEVEL? 3) MAINTAIN MINIMUM 3" CLEARANCE REBAR TO DIRT 4) SUPPORT VERTICAL REBAR IN PLACE 5) NO ANSWER AT DOOR 6) NO PLANS VISIBLE 7) RECALL AFTER ABOVE CORRECTED | |
09/17/2001 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*/ 1) PROVIDE MINIMUM OF 3" CLEARANCE AT REBAR FROM ENTRY 2) OVER LAP SHOULD BE 40 TIMES DIAMETER OF REBAR | |
09/11/2001 | BUILDING PRE-SLAB | Not ready for Inspection |