Permit: T01CM03849

Parcel: 10408086C


Addresses:

800 W AUTO MALL DR


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T01CM03849

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*
01/06/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) INSTALL APPROVED CLEAN OUT PLUGS AND COVERS AT STORAGE ROOM #17. 2.) CLEAN OTS FOR EDF AND UTILITY SINK REQUIRE 12" CLEARANCE INFRONT OF CLEAN OUT. 3.) BOTH WATER HEATERS REQUIRE HEAT TRAP FITTINGS. 4.) SUPPORT EXPANSION TANK IN PREP-ROOM#15. 5.) FINISH INSTALLING WASH FOUNTAIN IN TOILET ROOM #9