Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01CM03849
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
01/06/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) INSTALL APPROVED CLEAN OUT PLUGS AND COVERS AT STORAGE ROOM #17. 2.) CLEAN OTS FOR EDF AND UTILITY SINK REQUIRE 12" CLEARANCE INFRONT OF CLEAN OUT. 3.) BOTH WATER HEATERS REQUIRE HEAT TRAP FITTINGS. 4.) SUPPORT EXPANSION TANK IN PREP-ROOM#15. 5.) FINISH INSTALLING WASH FOUNTAIN IN TOILET ROOM #9 |