Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 05/20/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE NAIL/SCREW PROTECTION FOR ALL PLUMBING WITHIN 1 1/4" OF STUD SURFACE 2) SHEATHING WIRES MUST EXTEND INTO ELECTRIC BOXES AT LEAST 1/4" 3) SECURE WIRES AT 4' ON CENTER 4) FIRE BLOCK BY BREAK THRU 5) BATH VENT OUTSIDE OF WALL CAVITY 6) PROVIDE WHOLE HOUSE DWV WATER TEST PER UPC 712.2 7) HEADERS MUST BEAR ON TRIMMERS 8) FIRE STOP FLOOR PENETRATIONS 2ND FLOOR 9) FIRE BLOCK ALL DROP CEILING 10) CLOSET LIGHTS MUST BE 12" IN FRONT OF SHELFS 11) NO PLANS ON SITE, STOPPED INSPECTION |
| 05/08/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SHEAR CHANGE ON A-6 REQUIRED CITY OF TUCSON STAMP |