Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/08/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 04/26/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) RELOCATED AND EPOXIED HOLDOWNS-OK 2) YOU MUST HAVE THE PLAN REVISION FOR RELOCATING SHEAR PANELS TO INSIDE OF HOUSE APPROVED BY CITY OF TUCSON 3) NO EPOXY SPECIAL INSPECTION REPORT ON SITE |
| 04/18/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) HOLDOWN BOLTS CANNOT BE BENT OR DEFORMED. PROVIDE ENGINEERS AND CITY OF TUCSON APPROVAL OF REPAIR 2) HOLDOWNS REQUIRED TO BE SIMPSON PHD-8 METAL PRODUCT AD 5B INSTALLED. YOU MUST BUILD TO PLAN 3) SHEAR WALLS ARE NOT PER PLAN 4) STOPPED INSPECTION |
| 04/15/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) LEDGER CLIPS OK 2) PROVIDE CITY OF TUCSON APPROVAL FOR HOLDOWN CHANGE FROM HD 8A TO HD 5A |