Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T01CM03829
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2002 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
04/26/2002 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) RELOCATED AND EPOXIED HOLDOWNS-OK 2) YOU MUST HAVE THE PLAN REVISION FOR RELOCATING SHEAR PANELS TO INSIDE OF HOUSE APPROVED BY CITY OF TUCSON 3) NO EPOXY SPECIAL INSPECTION REPORT ON SITE | |
04/18/2002 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) HOLDOWN BOLTS CANNOT BE BENT OR DEFORMED. PROVIDE ENGINEERS AND CITY OF TUCSON APPROVAL OF REPAIR 2) HOLDOWNS REQUIRED TO BE SIMPSON PHD-8 METAL PRODUCT AD 5B INSTALLED. YOU MUST BUILD TO PLAN 3) SHEAR WALLS ARE NOT PER PLAN 4) STOPPED INSPECTION | |
04/15/2002 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) LEDGER CLIPS OK 2) PROVIDE CITY OF TUCSON APPROVAL FOR HOLDOWN CHANGE FROM HD 8A TO HD 5A |