Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01CM03818
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) WATER HEATER LOWERED. 2.) INDIRECT WASTE SPLASH CORRECTED. 3.) R.O. WATER HAS INTERNAL AIR GAP. 4.) OK FOR C OF O PENDING ANY OTHER INSPECTIONS. | |
05/31/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) INSTALL INDIRECT WASTE PIPING SO THERE IS NO SPLASHING DURING DISCHARGE INTO FLOOR SINK. 2.) WATER HEATERS INSTALLED OVER EIGHT FEET ABOVE FINISHED FLOOR REQUIRE PERMANENT LADDER FOR ACCESS. 3.) WITH REVERSE OSMOSIS TYING DIRECTLY INTO TAILPIECE OF SINK WHERE IS BACKFLOW/BACKS SIPHONAGE PROTECTION. | |
05/17/2002 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) 2 ITEMS ON BACK ORDER 2.) PLUMBING NEARING COMPLETION. 3.) NO OUTSTANDING ISSUES AT THIS TIME. | |
04/22/2002 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NOT READY FOR INSPECTION. |