Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM03793
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
01/16/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) A/C CONDENSOR REQUIRES MIN 12" CLEARANCE FROM WALL 2) CLEANOUTS NOT PROPERLY TERMINATED 3) SEAL AROUND RETURN AIR PLENIUM PENETRATIONS 4) RELOCATE OUTLET IN MASTER BATH |