| 11/15/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/12/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NOT READY 1.) LIST TAKEN BY GENL. 1.) DISCONNECT ON AH UNITS & WTR HTR. 2.) LABELS DISCONNECTS W/PNL & CKTS SERVING 3.) BOND DUCT AT AH UNITS. 4.) LABEL MAGNETIC STARTERS & OPERATING SWITCHES. 5.) REMOVE EXTENSION CORD AT COOLERS & REPLACE WITH SEAL TITE FLEX. 6.) LEAVE EYS LOOSE OR OFF AT PAINT BOOTHS. |