Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01CM03755
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2002 | ELECTRIC - CABLE DROP | Approved | ||
| 10/08/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0210*DISCUSSED W/CONTRACTOR. | |
| 09/20/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0215*NOT READY SEE ELECT. SPECS SHT. E2 NOTE 4. THE PLANS REQUIRE STEEL CONDUIT ABOVE GROUND. THE 2 4" PVC CONDUITS FOR SERVICE ENTRANCE ARE SET TO SHALLOW. IF RIDGID IRON CONDUIT IS USED THE DEPTH WILL BE ACCEPTABLE SEE BELOW. 1.) THE ELECTRICAL SERVICE EQUIPMENT IS NOT GROUNDED PER NE CODE ART 250 AND IS NOT ACCEPTABLE AS INSTALLED. 2.) INSTALL UNISTRUT CLAMPS TO SECURE THE CONDUITS FROM DISCONNECTS. I WILL BE AVAILABLE TO CONSULT WITH ELECTRCIAL CONTRACTOR REGARDING SERVICE EQUPMT. |