Permit: T01CM03755

Parcel: 130070020


Addresses:

3810 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01CM03755

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2002 ELECTRIC - CABLE DROP Approved
10/08/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0210*DISCUSSED W/CONTRACTOR.
09/20/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*NOT READY SEE ELECT. SPECS SHT. E2 NOTE 4. THE PLANS REQUIRE STEEL CONDUIT ABOVE GROUND. THE 2 4" PVC CONDUITS FOR SERVICE ENTRANCE ARE SET TO SHALLOW. IF RIDGID IRON CONDUIT IS USED THE DEPTH WILL BE ACCEPTABLE SEE BELOW. 1.) THE ELECTRICAL SERVICE EQUIPMENT IS NOT GROUNDED PER NE CODE ART 250 AND IS NOT ACCEPTABLE AS INSTALLED. 2.) INSTALL UNISTRUT CLAMPS TO SECURE THE CONDUITS FROM DISCONNECTS. I WILL BE AVAILABLE TO CONSULT WITH ELECTRCIAL CONTRACTOR REGARDING SERVICE EQUPMT.