Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/15/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/28/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OFFICE 1ST & 2ND FLRS. ROUGH IN OK. |
| 08/23/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*2ND FLOOR ELECTRIC ROUGH IN OF WALLS OK. GIVE YOUR LAYOUT A FINAL CHECKOUT BEFORE DRYWALL IS APPLIED. CORRECTIONS REQUIRED. 1.) INSTALL 4'S J-BOX FOR MC CABLES IN CIELING OF BATHROOMS. FLOURESCENT FIXTURES ARE NOT APPROVED FOR USE AS J-BOXES ONLY FOR FEED THRU FOR USE AS J-BOXES ONLY FOR FEED THRU TO ABUTTING FIXTURES WHEN APPROVED OR LISTED FOR THE PURPOSE. 2.)INSTALL RECESSED LITE CANS PROPERLY. FASTEN BRACKETS TO WOOD FRAME. CAN RIM MUST FIT FLUSH WITH DRYWALL SURFACE. 3.) KEEP MC AWAY FROM COPPER WATER PIPE. 4.) STRAP MC CABLE, FOR FAU FEEDER, TO 2 X 4'S WITHIN. 8" OF EA BOX AND EVERY FOUR 4' FEET. 5.) COMPLETE FEED CABLE TO FLOOR BOXES. 6.) CHECK YOUR LAYOUT TO PLAN THANK YOU. |