Permit: T01CM03749

Parcel: 11304299F

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
09/17/2001 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
09/10/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) NEED TO EXTEND COMBUSTION/RELIEF AIR FROM 1ST FLR. UP THROUGH ROOF. DO NOT HAVE 30" IN ATTIC/NON VENTED ATTIC. 2.)RETURN AIR PLENUIMS, 1ST FLR. NEEED TO SHEET ROCK INTERIOR. NO COMBUSTIBLES IN A RETURN PLENIUM CORRECT/RECALL