Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/04/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 04/01/2002 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) YOU HAVE PROBLEMS FROM LAST INSPECTION (A) YOU CANNOT USE SAN "T"'S LAYING FLAT, USE A COMBO OR A WYE FITTING WITH 1/8 BEND (B) DONOT USE (1/4 SHORT BENDS) FOR SOIL PIPE RADIUS, USE LONG SWEEPS 2) BATHROOM LAYOUT 2 TOILET, TWO TUBS-TWO LAVS I ONLY SEE ONE TUB/TRAP ? OR YOU MOVED EAST TUB DRAIN, EITHER WAY TRAP FIXTURE FARTHEST EAST ( INSIDE EXISTING) IS TO FAR AWAY FROM VENT 2" MAX IS 5'-0", ONE OF YOUR TOILETS IS BEING VENTED FROM A TRUNK LINE 3) OUT SIDE YOU USE A REDUCING CLOSET BEND FITTING FOR A HORIZONTAL 90 DEGREE, USE A LONG SWEEP THERE 4) TRY TO FIND A PLUMBER TO HELP YOU. |
| 03/27/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) SANITARY T FITTINGS NOT ALLOWED TO BE INSTALLED IN HORIZONTAL DRAIN 2) VENT 90 NOT ALLOWED BELLOW 42" ABOVE F.F. 5) TRUNK VENTING OF WATER CLOSETS NOT ALLOWED |