Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/23/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 12/31/2001 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) JOINTS STILL LEAKING 2) ELECTRICAL TAPE ISN'T AN APPROVED MATERIAL FOR ABS CONNECTIONS |
| 12/27/2001 |
PLUMBING - ROUGH, SOIL |
|
Cancelled |
IVRS - Ri canceled |
| 12/20/2001 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) LOOKS LIKE YOU HAVE 3 LEAKING JOINTS 1.) AT C.O. BOMB 2.) AT 2" TO 3" HORIZ COMBO FROM KIT SINK 1/8 BEND WEST OF SHOWER VENT. 2.) DIG OUT DIRT BELOW LEAK WIPE WITH A RAG. FEEL FOR H20 |
| 12/19/2001 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) REPLACE ALL SAN-TEE'S WITH COMBINATION FITTINGS (ALL SAN-TEE'S LYING FLAT) 2) NEED A TWO WAY CLEANOUT FITTING FOR MAIN CLEANOUT OR USE TWO COMBOS |